84 UDC 6300 Process Controller Product Manual 1/03
4.6 Algorithm Data Set Up Group, Continued
Table 4-5 Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
CONT ALG
continued
3 POS STEP
THREE POSITION STEP - The Three Position Step
Control algorithm allows the control of a valve (or other
actuator) with an electric motor. Digital Outputs 3 and
4 generate control signals that drive external relays;
one to move the motor upscale, the other to move it
downscale, without a feedback slidewire linked to the
motor shaft.
3PSTEP is an extension of the On-Off Duplex Control
and includes internal feedback of the state of the
Digital Outputs.
In this algorithm, the error signal is compared with a
feedback signal and the result determines the state of
the Digital Outputs as follows:
Positive Error > Feedback Digital Output 3 On
Negative Error < Feedback Digital Output 4 On
Otherwise, the outputs are both off.
The 3PSTEP control algorithm provides an output
display (“OUT”) which is an estimated motor position
since the motor is not using any slidewire feedback.
Select a Motor Travel Time at prompt “MTR TIME”.
M/A STN
MANUAL/AUTO STATION—Provides an operator display for
the TDC PID loop PV, SP, OP and MODE. The UDC loop
has only Manual control at the UDC6300. Auto mode for the
loop is maintained in the TDC.
If you select Auto mode at the UDC, the MAN indicator will
blink, indicating AUTO is not available.
When the TDC provides an output override value, MAN
indicator will turn OFF.
AUTO indicator is never displayed. Output override does not
necessarily mean that the loop is in AUTO.
Other configuration settings required:
Setup CONTROL prompt PV SOURCE = NONE.
Setup CONTROL prompts SPHILIM, SPLOLIM = PV and SP
range (for bargraph).
Refer to Manual/Auto Station Addendum 51-52-99-08 for
implementation details.
MTR TIME
(appears only if 3POS
STEP is selected
above)
5 to 255 in seconds
THREE POSITION STEP MOTOR TRAVEL TIME -
this is the time it takes the motor to travel from 0% to
100%
Refer to Subsection 5.21 - Three Position Step Control
for complete configuration and operating instructions.