120 UDC 6300 Process Controller Product Manual 1/03
4.13 Options Set Up Group
Introduction
Configure the Digital Inputs to a specific contact closure response, or
configure the 2nd Current Output to be a specific selection with desired
scaling.
Table 4-12 lists all the function prompts in the Option setup group and
their functions.
Table 4-12 Option Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
CUR OUT 2
2ND CURRENT OUTPUT—primarily is used for
Loop 2 output but it also can represent one of
13 control parameters. The display for 2nd current
output viewing will be in engineering units for all but
output. Output will be in percent.
Other prompts affected by these selections: "4mA
VAL" and "20mA VAL."
DISABL
NO 2nd CURRENT OUTPUT
INPUT 1
INPUT 1 represents the value of the configured
range of input 1.
INPUT 2
INPUT 2 represents the value of the configured
range of input 2.
INPUT 3
INPUT 3 represents the value of the configured
range of input 3.
INPUT 4
INPUT 4 represents the value of the configured
range of input 4.
INPUT 5
INPUT 5 — This represents the configured range of
input 5. FOR EXAMPLE:
Type “J” Thermocouple (0 to 1600°F)
0°F display = 0% output
1600°F display = 100% output
PV
PROCESS VARIABLE — Represents the value of
the Process Variable for Loop 1.
DEVIATION
DEVIATION (PROCESS VARIABLE MINUS
SETPOINT) — Represents –100 to +100% of the
selected PV span in engineering units for Loop 1.
When Deviation is selected, only one operating
parameter will be entered. This value represents the
deviation level that will produce 20mA output. Zero
deviation will produce a center scale (12mA) output. A
negative deviation equal in magnitude to the 2nd current
output high value will produce a low end (4mA) output.
OUTPUT
OUTPUT — Represents the displayed controller
output in percent (%) for Loop 1.
SP
SETPOINT — Represents the value of the setpoint
in units of PV for Loop 1.
Table 4-12 continued on next page