92 UDC 6300 Process Controller Product Manual 1/03
4.6 Algorithm Data Set Up Group, Continued
Table 4-5 Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
8 SG CHAR2
DISABLE
INPUT 2
LOOP 1 OUT
LOOP 2 OUT
INPUT4
Note: The X values below
should be entered as
increasing values
(from 0% to 100%)
from N=0 to 8
8 SEGMENT CHARACTERIZER #2 - A second
eight segment characterizer can be applied to either
Input 2, Output 1, Output 2, or Input 4.
DISABLE - disables characterizer
INPUT 2 - characterizer applied to Input 2
LOOP 1 OUT - characterizer applied to Loop 1
Output
LOOP 2 OUT - characterizer applied to Loop 2
Output
INPUT 4 - characterizer applied to Input 4.
There are 8 (Xn) Input values and 8 (Yn) Output
values to be selected. The following rules apply:
• When Input 2 is used, Input 2 Ratio and Bias are
applied to the Xn Values.
• When one of the Loop outputs are selected, the Xn
Input values are the Output from the control
algorithm, and the Yn Output is the final control
element action. This application is useful for non-
linear control elements or Process Variable.
A simple example is shown in Figure 4-2.
X0 VALUE2
0.00 to 99.99%
X0 INPUT VALUE (X AXIS)
X1 VALUE2
0.00 to 99.99%
X1 INPUT VALUE (X AXIS)
X2 VALUE2
0.00 to 99.99%
X2 INPUT VALUE (X AXIS)
X3 VALUE2
0.00 to 99.99%
X3 INPUT VALUE (X AXIS)
X4 VALUE2
0.00 to 99.99%
X4 INPUT VALUE (X AXIS)
X5 VALUE2
0.00 to 99.99%
X5 INPUT VALUE (X AXIS)
X6 VALUE2
0.00 to 99.99%
X6 INPUT VALUE (X AXIS)
X7 VALUE2
0.00 to 99.99%
X7 INPUT VALUE (X AXIS)
X8 VALUE2
0.00 to 99.99%
X8 INPUT VALUE (X AXIS)
Y0 VALUE2
0.00 to 99.99%
Y0 INPUT VALUE (Y AXIS)
Y1 VALUE2
0.00 to 99.99%
Y1 INPUT VALUE (Y AXIS)
Y2 VALUE2
0.00 to 99.99%
Y2 INPUT VALUE (Y AXIS)
Y3 VALUE2
0.00 to 99.99%
Y3 INPUT VALUE (Y AXIS)
Y4 VALUE2
0.00 to 99.99%
Y4 INPUT VALUE (Y AXIS)
Y5 VALUE2
0.00 to 99.99%
Y5 INPUT VALUE (Y AXIS)
Y6 VALUE2
0.00 to 99.99%
Y6 INPUT VALUE (Y AXIS)
Y7 VALUE2
0.00 to 99.99%
Y7 INPUT VALUE (Y AXIS)
Y8 VALUE2
0.00 to 99.99%
Y8 INPUT VALUE (Y AXIS)
Continued on next page