1/03 UDC 6300 Process Controller Product Manual 59
3.17 Options Set Up Group, Continued
Function prompts,
continued
Table 3-14 lists all the function prompts in the “Options” Set Up group.
Table 3-14 Options Group Function Prompts, continued
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
DIG1 COMB
Digital Input 1
Combinations
DISABLE
+TO PID2
+TO DIR
+TO SP2
+DIS ADT1
+TO SP1
+TO RUN
DISABLE
DIG IN 2
Digital Input 2 selections
Same as DIG IN 1
NONE
DIG 2 COMB
Digital Input 2
Combinations
DISABLE
+TO PID2
+TO DIR
+TO SP2
+DIS ADT2
+TO SP1
+TO RUN
DISABLE
DIG IN 3
Digital Input 3 selections
NONE
TO MANUAL
TO SP1
TO SP2
TO SP3
TO RUN
TO HOLD
TO PID2
PV IS IN1
PV IS IN2
PV IS IN3
PV IS IN4
PV IS IN5
RSP - IN1*
RSP - IN2
RSP - IN3
RSP - IN4
RSP - IN5
TO DIRECT
MAN FSAFE
ToA/M STA
TO PURGE
LOW FIRE
* Digital Input Only
NONE
DIG IN 4
Digital Input 4 selections
Same as DIG IN 3
NONE
DIG IN 5
Digital Input 5 selections
Same as DIG IN 3
NONE
DIG IN 6
Digital Input 6 selections
Same as DIG IN 3
NONE
DI ON LP1
Assigned to Loop 1
DI3,4,5,6
DI3,4,5
DI3,4
DI3
DI3,4,5,6
LATCHING
Purge/Low Fire action
NONE, PURGE, LOW FIRE,
BOTH
NONE