1/03 UDC 6300 Process Controller Product Manual 61
3.18 Communications Group, Continued
Function prompts,
continued
Table 3-15 Commun Group Function Prompts, continued
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
DUPLEX
Does not apply to
485TDCSDI
Transmission Response HALF
FULL
FULL
DATA FORM
485MODRTU only
Transmission Data Format INTEGER
FLOAT POINT
INTEGER
UNITS
Communication Units PERCENT
ENG
PERCENT
BOX MODE
Overall Mode of UDC6300
Operation
BASIC MODE
FULL MODE
FULL
SHEDTIME
Shed Time 1 to 255 sample periods
0 = No Shed
0
SHEDMODE
Shed Controller Mode and
Output Level for Loop 1
LAST
TO MAN
FSAFE
ToAUTO
LAST
SHED SP
Shed Setpoint Recall for
Loop 1
TO LSP
TO CSP
TO LSP
CSP RATIO
Loop 1 Computer Setpoint
Ratio
–20.00 to 20.00 1.00
CSP BIAS
Loop 1 Computer Setpoint
Bias
–999.0 to 9999 0.0
RCASMODE
485TDCSDI only
Remote Cascade Option for
Loop 1
SPC
DDC
M/A STN
SPC
SHED2MODE
Shed Controller Mode and
Output Level for Loop 2
LAST
TO MAN
FSAFE
ToAUTO
LAST
SHED2 SP
Shed Setpoint Recall for
Loop 2
TO LSP
TO CSP
TO LSP
CSP2 RATIO
Loop 2 or Cascade Computer
Setpoint Ratio
–20.00 to 20.00 1.00
CSP2 BIAS
Loop 2 or Cascade Computer
Setpoint Bias
–999.0 to 9999 0.0
RCAS2MOD
485TDCSDI only
Remote Cascade Option for
Loop 2
SPC
DDC
M/A STN
SPC
TEST COM
(replaces LOOPBACK)
Test Communications DISABL
ENABLE
DISABL
Vista de pagina 74