1/03 UDC 6300 Process Controller Product Manual 37
3.7 Tuning L2 Parameters Set Up Group (Cascade or 2
Loop)
Function prompts
Table 3-4 lists all the function prompts in the Tuning L2 Set Up group.
This group is only displayed if the controller is configured for "Cascade"
or
"2 Loop" control at prompt "PV2SCR"
Table 3-4 Tuning L2 Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
PROPBAND3
or
GAIN3
Proportional Band 3, or
Gain 3
0.1 to 9999 (PB)
0.001 to 1000 (Gain)
- -
1.0
GAIN VALn
Gain Value being used by
Gain Scheduling when
enabled
Read Only - -
RATE 3 MIN
Rate 3 in Minutes 0.00 to 10.00 minutes (0.00=Off) 0.00
RESET3MIN
RESET3RPM
Reset 3 in minutes/repeat
Reset 3 in repeats/minute
0.02 to 50.00
0.02 to 50.00
1.0
- -
MAN RESET3
Manual Reset 3 –100 to 100% Output 0.0
PROPBAND4
or
GAIN 4
Proportional
Band 4, or
Gain 4
0.1 to 9999 (PB)
0.001 to 1000 (Gain)
- -
1.0
RATE4MIN
Rate 4 in Minutes 0.00 to 10.00 minutes (0.00=Off) 0.00
RESET4MIN
RESET4RPM
Reset 4 in minutes/repeat
Reset 4 in repeats/minute
0.02 to 50.00
0.02 to 50.00
1.0
- -
CYC 3SEC
Cycle Time 3 (Heat) 1 to 120 seconds 4
CYC4 SEC
Cycle Time 4 (Cool) 1 to 120 seconds 4
PVEU VAL1
PV1 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
PVEU VAL2
PV2 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
PVEU VAL3
PV3 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
PVEU VAL4
PV4 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
PVEU VAL5
PV5 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
PVEU VAL6
PV6 Value for Gain
Scheduling
PV value within the PV limits.
In Engineering units
0
Table 3-4 continued on next page