62 UDC 6300 Process Controller Product Manual 1/03
3.19 Alarms Set Up Group
Introduction
This data deals with the Alarms function that is available with your
controller.
There are up to four alarms available. Each alarm has two setpoints.
You can configure each of these two setpoints to alarm on one of several
events, and you can configure each setpoint to alarm High or Low.
ATTENTION
Alarm 1 = Digital Output 1
Alarm 2 = Digital Output 2
Alarm 3 = Digital Output 3
Alarm 4 = Digital Output 4
Function prompts
Table 3-16 lists all the function prompts in the “Alarms” Set Up group.
Table 3-16 Alarms Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
A1S1 VALU
Alarm 1, Setpoint 1
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
90
A1S2 VALU
Alarm 1, Setpoint 2
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
10
A2S1 VALU
Alarm 2, Setpoint 1
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
95
A2S2 VALU
Alarm 2, Setpoint 2
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
5
A3S1 VALU
Alarm 3, Setpoint 1
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
90
A3S2 VALU
Alarm 3, Setpoint 2
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
10
A4S1 VALU
Alarm 4, Setpoint
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
95
A4S2 VALU
Alarm 4, Setpoint 2
Value
Within the range of selected
parameter or PV Span for
Deviation Alarm
5
Table 3-16 continued on next page