214 UDC 6300 Process Controller Product Manual 1/03
5.23 Auto/Manual Station, Continued
Configuration
(continued)
Refer to Table 5-46 and set up the controller in the order shown.
Table 5-46 Auto/Manual Station Mode Configuration Procedure
Step
Press
SET
UP
to Select
Setup Group
Press
FUNC
to Select
Function
Prompts
Press s t
Enter
Value or
Selection
Remarks
1 Control
PID SETS 2 KEYBD Select other control parameters as needed by
LSP’s TWO
the application.
SP TRACK NONE
2 Algorithm
CONTR ALG PD+MR This allows setting of the Manual Reset value.
3 Tuning
MAN RESET 0 Manual Reset of 0 for no output Bias and
requires LSP2=0%. If Bias is required, set MR
to equal the desired output Bias value.
4 Algorithm
CONT ALG PID A Defines Back-up Control Algorithm.
5 Tuning
RSET2MIN 50.00
GAIN2 See Note 1 Note 1. Set the Gain 2 equal to
Input 1 Span
Input 2 Span
If “PB” is selected under “Control” setup group,
function prompt “PBorGAIN”, set the PROP BD2
to
100 x
Input 2 Span
Input 1 Span
RATE2MIN 0.00 Select PIDSET1 tuning parameters as needed
by the application.
6 Options
DIG IN1 through
DIG IN 6
AM STA
CAUTION
DO NOT SELECT
• In the CONTROL setup list, do not select SP TRACK as PV or RSP.
• In the SP RAMP setup list, do not select SP RATE as ENABLE.
• In the ALGORTHM setup list, do not select CONT ALG as
PID B, ON-OFF, or 3PSTEP.
• In the Display menu when PIDSET# is displayed, DO NOT change the
selection.
Continued on next page