214 UDC 6300 Process Controller Product Manual 1/03
5.23 Auto/Manual Station, Continued
Configuration
(continued)
Refer to Table 5-46 and set up the controller in the order shown.
Table 5-46 Auto/Manual Station Mode Configuration Procedure
Step
Press
SET
UP
to Select
Setup Group
Press
FUNC
to Select
Function
Prompts
Press s t
Enter
Value or
Selection
Remarks
1 Control
PID SETS 2 KEYBD Select other control parameters as needed by
LSP’s TWO
the application.
SP TRACK NONE
2 Algorithm
CONTR ALG PD+MR This allows setting of the Manual Reset value.
3 Tuning
MAN RESET 0 Manual Reset of 0 for no output Bias and
requires LSP2=0%. If Bias is required, set MR
to equal the desired output Bias value.
4 Algorithm
CONT ALG PID A Defines Back-up Control Algorithm.
5 Tuning
RSET2MIN 50.00
GAIN2 See Note 1 Note 1. Set the Gain 2 equal to
Input 1 Span
Input 2 Span
If “PB” is selected under “Control” setup group,
function prompt “PBorGAIN”, set the PROP BD2
to
100 x
Input 2 Span
Input 1 Span
RATE2MIN 0.00 Select PIDSET1 tuning parameters as needed
by the application.
6 Options
DIG IN1 through
DIG IN 6
AM STA
CAUTION
DO NOT SELECT
In the CONTROL setup list, do not select SP TRACK as PV or RSP.
In the SP RAMP setup list, do not select SP RATE as ENABLE.
In the ALGORTHM setup list, do not select CONT ALG as
PID B, ON-OFF, or 3PSTEP.
In the Display menu when PIDSET# is displayed, DO NOT change the
selection.
Continued on next page