108 UDC 6300 Process Controller Product Manual 1/03
4.10 Input 5 Parameters Set Up Group
Introduction
These are the parameters required for optional input 5 which can be a
Direct Thermocouple, RTD, or Pulse Input; Type, Input 5 Pulse,
Transmitter Characterization, High and Low range values in engineering
units, Ratio, Bias, Filter, Burnout, and Emissivity.
Input 5 group prompts
Table 4-9 lists all the function prompts in the Optional Input 5 setup group
and their definitions.
Table 4-9 Input 5 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN 5 TYPE
ATTENTION
Change of input type
selection results in
loss of any field
calibration and
restores factory
calibration.
DISABLE
B TC
E TC
J TC
K TC
NNM
NIC TC
R TC
S TC
T TC
W TC
100 PT
100 LO PT
200PT
500PT
RH RADIAM
MILLIAMPS
0–10 MV
10–50 MV
1–5V
0–10V
PULSE
INPUT 5 ACTUATION TYPE - This selection
determines what actuation you are going to use for
Input 5.
DISABLE - Disable Input 5
B TC - B Thermocouple
E TC- E Thermocouple
J TC- J Thermocouple
K TC- K Thermocouple
NNM- NiNiMo Thermocouple
NIC TC- Nicrosil Nisil Thermocouple
R TC- R Thermocouple
S TC- S Thermocouple
T TC- T Thermocouple
W TC- W Thermocouple
100 PT - 100 Ohm RTD High
100 LOW - 100 Ohm RTD Low
200PT- 200 Ohm RTD
500PT- 500 Ohm RTD
RH RADIAM - Radiamatic ( type RH only)
4 to 20 MILLIAMPS*
0 TO 10 MILLIVOLTS*
10 TO 50 MILLIVOLTS*
1 TO 5 VOLTS*
0 TO 10 VOLTS*
PULSE - 0 to 25 Khz (automatically selected when a
pulse Input board is installed).Minimum Span 100Hz
* Linear Range
IN5 PULSE
DISABLE
FREQ INP
PULSE
INPUT 5 PULSE ACTUATION - available only when
a Pulse Input board is installed.
DISABLE - disables Input 5
FREQUENCY INPUT - for Flow Transmitters
PULSE - for Setpoint/Remote Setpoint adjustments.
Refer to "Operation" section for operational
overview.
Table 4-9 continued on next page