1/03 UDC 6300 Process Controller Product Manual 39
3.8 SP Ramp/Program Set Up Group
Single Setpoint Ramp
The Setpoint Ramp Set Up group contains the Function parameters that let
you configure a single set point ramp to occur between the current local
setpoint and a final setpoint over a time interval (SP RAMP).
Setpoint rate
The Setpoint Ramp Set Up group also contains the function parameters
that let you configure a specific rate of change for any Local Setpoint
change (SP RATE). It includes selections for Rate Up and Rate Down.
Function prompts
Table 3-5 lists all the function prompts in the SP RAMP Set Up group.
Table 3-5 SP Ramp Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
SP RAMP
Single Setpoint Ramp
Selection
DISABLE
ENABLE
ENABLE 2
ENABLE 12
DISABLE
TIME MIN
Single Setpoint Ramp
Time
0 to 255 minutes 3
FINAL SP
Single Setpoint Final
Setpoint
Enter a value within the setpoint
limits
1000
SP RATE
Setpoint Rate DISABLE
ENABLE
ENABLE 2
ENABLE 12
DISABLE
EU/HR UP
Rate Up Value for
Loop 1 (SP Rate Enabled)
0 to 9999
in Units per Hour
0
EU/HR DN
Rate Down Value for
Loop 1 (SP Rate Enabled)
0 to 9999
in Units per Hour
0
EU/HR UP2
Rate Up Value for
Loop 2 (SP Rate Enabled)
0 to 9999
in Units per Hour
0
EU/HR DN2
Rate Down Value for
Loop 2 (SP Rate Enabled)
0 to 9999
in Units per Hour
0