8 UDC 6300 Process Controller Product Manual 1/03
2.1 Overview, Continued
Pre-installation
information
If the controller has not been removed from its shipping carton, inspect
the carton for damage and remove the controller. Inspect the unit for any
obvious shipping damage and report any damage due to transit to the
carrier.
Make sure a bag containing mounting hardware is included in the carton
with the controller.
Check that the model number shown on the inside of the case agrees with
what you have ordered.
CE Conformity
special conditions
(Europe)
Shielded twisted pair cables are required for all Analog I/O, Process
Variable, RTD, Thermocouple, dc millivolt, low level signal, 4-20 mA,
Digital I/O, and computer interface circuits. For performance Criterion A
under special conditions, DO NOT set alarm outputs to LATCHING (ref.
Sections 3.19, 4.15, and 5.17)
Refer to Appendix B - Severe Electrical Noise Environments for
additional installation guidance.
Operating limits
We recommend that you review and adhere to the operating limits listed
in Table 2-1 when you install your controller.
Table 2-1 Operating Limits
Condition Specifications
Ambient Temperature 32 to 140°F (0 to 60°C)
Relative Humidity 5 to 90% RH at 40°C (104°F)
Vibration
Frequency
Acceleration
0 to 200Hz
0.2g
Mechanical Shock
Acceleration
Duration
5g
30ms
Power
Voltage
Frequency(Hz)
20 to 30 Vac/dc
96 to 132 Vac
192 to 264 Vac
49 to 51
59 to 61
Transmitter Supply
Voltage (at input
terminals)
22 to 26 Vdc
@ 50mA
Power Consumption 20VA Maximum