1/03 UDC 6300 Process Controller Product Manual 75
4.2 Tuning Parameters Set Up Group, Continued
Table 4-1 Tuning Group Prompt Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
GAIN VAL 1
GAIN VAL 2
GAIN VAL 3
GAIN VAL 4
GAIN VAL 5
GAIN VAL 6
GAIN VAL 7
GAIN VAL 8
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
Gain Value 1 for Gain
Scheduling
GAIN VAL 1 is the first of 8 user-defined Gain
values.
Enter a Gain Value you want to be used with "PVEU
VAL n" previously entered.
To complete the Gain selections, enter a Gain value
for all the GAIN VAL prompts listed.
The table below shows the relationship between the
GAIN Values and the PVEU Values.
Gain PV Band over which each Gain
Value X applies
1 Low range limit to PVEU VAL2
2 PVUE VAL2 to PVEU VAL3
3 PVUE VAL3 to PVEU VAL4
4 PVUE VAL4 to PVEU VAL5
5 PVUE VAL5 to PVEU VAL6
6 PVUE VAL6 to PVEU VAL7
7 PVUE VAL7 to PVEU VAL8
8 PVUE VAL8 to High Range Limit
ATTENTION
When PB is configured (instead of
Gain) in the "CONTROL" group prompt "PB or
GAIN", the displayed "GAIN VALn" is in units of
%PB.