
194 UDC 6300 Process Controller Product Manual 1/03
5.18 Digital Input Option (Remote Switching), Continued
Digital input 1 and 2
combination
selections
The Digital Input combination selections listed in Table 5-33 and 5-34 can
be used in combination with the Digital Inputs 1 and 2 listed in Table 5-
32.
Refer to Section 3 - Configuration and make your selections under Set Up
prompt “OPTIONS”; Function prompt “DIG 1 COMB” or “DIG 2
COMB”
Table 5-33 Digital Input Combinations “DIG IN 1”
Selections used in
Combination with
“DIG IN1”
Display Indication Action on contact closure*
+ To PID2
Lower Display = PID SET 2 Selects PID 2.
+To DIRECT
“1” or “2” blinks Puts the controller into direct controller action.
+ To SP2
“SP2” blinks Selects the Second Local Setpoint
+ DIS ADT1
“T” no longer lighted Disable Adaptive tune - Loop 1.
+ To SP1
“SP” blinks Selects the local setpoint.
To RUN
“R” indicator blinks Starts or restarts RUN of SP Ramp.
*Returns (toggles) to original state when contact opens.
Table 5-34 Digital Input Combinations “DIG IN 2”
Selections used in
Combination with
“DIG IN2”
Display Indication Action on contact closure*
+ To PID2
Lower Display = PID SET 2 Selects PID 2.
+To DIRECT
“1” or “2” blinks Puts the controller into direct controller action.
+ To SP2
“SP2” blinks Selects the second local setpoint.
+ DIS ADT2
“T” no longer lighted Disable Adaptive tune - Loop 2.
+ To SP1
“SP” blinks Selects the local setpoint.
To RUN
“R” indicator blinks Starts or restarts RUN of SP Ramp.
*Returns (toggles) to original state when contact opens.
Continued on next page
Comentarios a estos manuales