168 UDC 6300 Process Controller Product Manual 1/03
5.9 Single Setpoint Ramp, Continued
Procedure, continued
Table 5-18 Procedure for Running a Setpoint Ramp, continued
Step Operation Press Action
6
Change
setpoint during
HOLD mode
or
to change the "HELD" setpoint if the
ramp is on "HOLD".
However, the ramp time remaining is not
changed. Therefore, when returning to
RUN mode, the setpoint will ramp at the
same rate as previous to Local setpoint
changes and will stop if the Final
setpoint is reached before time expires.
If the time expires before the final
setpoint is reached, it will jump to the
final setpoint.
6
End the Ramp When the final setpoint is reached, the
“R” changes to “H” in the upper display
and the controller operates at the new
setpoint.
ATTENTION
Anytime the local
setpoint is different from the final
setpoint value and the FUNC
and
key is pressed - the ramp will start
again.
7
Disable the
setpoint ramp
function
SET
UP
Until you see:
SP RAMP
Lower Display
SET UP
Upper Display
FUNC
L1/L2
You will see:
SP RAMP
Lower Display
Upper Display
Enable
Enable 2
Enable 12
–SP Ramp for Loop 1
–SP Ramp for Loop 2
–SP Ramp for
Loops 1 and 2
Until you see:
SP RAMP
Lower Display
DISABL
Upper Display
8
Return to
normal
operating
mode
LOWR
DISP