3.13 Input 1 Through 4 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 1
through 4. The number of the Input group you are working with will
appear in each prompt.
Function prompts
Table 3-10 lists all the function prompts in the “INPUT 1 through 4” Set
Up groups.
Table 3-10 Input 1 through 4 Set Up Groups Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
XMITTERn
n = 1, 2, 3, or 4
Transmitter
Characterization
ATTENTION
Change
of input characterization
selection results in loss of
any field calibration and
restores factory calibration
of linear range 1 to 5
Volts.
DISABLE
B TC T TC
E TC W TC
J TC 100 PT
K TC 100 PT LO
NNM TC 200 PT
NIC TC 500 PT
R TC LINEAR
S TC
SQROOT
IN2 No R/B(Xmitter 4
only)
LINEAR
INn HIGH
n = 1, 2, 3, or 4
Input n High Range Value
(Adjustable for Linear or
Square Root
characterization only)
–999 to 9999
in engineering units
1000
INn LOW
n = 1, 2, 3, or 4
Input n Low Range Value
(Adjustable for Linear or
Square Root
characterization only)
–999 to 9999
in engineering units
0
RATIO n
n = 1, 2, 3, or 4
Input n Ratio Value –20.00 to 20.00
1.0
BIAS IN n
n = 1, 2, 3, or 4
Input n Bias Value –999 to 9999. 0
FILTER n
n = 1, 2, 3, or 4
Input n Filter 0 to 120 seconds 0
DEADTIME3 Deadtime for Input 3 only
0.0 to 60.0 Minutes 0
Table 3-10 continued on next page