1/03 UDC 6300 Process Controller Product Manual 131
4.14 Communications Set Up Group, Continued
Table 4-13 Communications Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
BOX MODE
Overall Mode of UDC6300
Operation
BASIC
FULL
BOX MODE — You can set the overall mode of operation
which will determine the level of interaction allowed from
the TDC to the UDC6300.
BASIC MODE — Permits only monitor operation from the
TDC.
FULL MODE — Permits control operations including mode
changes and Output and Setpoint overrides.
SHEDTIME
1 to 255
SHED TIME — The number that represents how many
sample periods there will be before the controller sheds
from communications. Each period equals 1/3 second or
0 = No shed.
SHEDMODE
LAST
TO MAN
FSAFE
ToAUTO
SHED CONTROLLER MODE AND OUTPUT LEVEL
FOR LOOP 1
— Determines the mode of local control you
want when the controller is shed from the communications
link.
LAST — SAME MODE AS BEFORE SHED — The
controller will return to the same mode (manual or
automatic) that it was in before shed.
TO MAN — TO MANUAL MODE BUMPLESS OUTPUT —
The controller will return to manual mode at the same
output level that it had before shed.
FAILSAFE — TO MANUAL MODE, FAILSAFE OUTPUT
— The controller will return to manual mode at the output
value selected at “CONTROL” prompt “FAILSAFE”.
ToAUTO — To automatic mode.
SHED SP
TO LSP
TO CSP
SHED SP FOR LOOP 1 — Shed setpoint recall.
TO LSP — Controller will use last local SP used.
TO CSP — Controller will use computer setpoint.
CSP RATIO
–20.00 to 20.00
LOOP 1 COMPUTER SETPOINT RATIO Computer
Setpoint ratio for Loop 1.
CSP BIAS
–999.0 to 9999
LOOP 1 COMPUTER SETPOINT BIAS Computer
Setpoint Bias for Loop 1.
RCASMODE
485TDCSDI only
SPC
DDC
M/A STN
REMOTE CASCADE OPTION FOR LOOP 1 — Lets you
select a Remote Cascade control architecture.
SPC (Supervisory Control) — The setpoint of the
secondary controller is controlled by a higher level
(Primary) controller.
DDC (Direct Digital Control) — The Output of the
secondary controller is controlled by the Output of the
higher level (Primary) controller.
MANUAL AUTO STATION—Allows the control loop to
behave as a Manual Auto Station whereby only manual
control is available at the UDC and Auto control is
performed in a computer or PLC.
Table 4-13 continued on next page