
1/03 UDC 6300 Process Controller Product Manual 151
5.4 Monitoring Your Controller, Continued
Viewing the operating
parameters,
continued
Table 5-4 Lower Display Key Parameter Prompts, continued
LOWER
DISPLAY
INDICATION
(XXXX = Value)
DEFINITION REMARKS
OC1
LOOP1 OUTPUT
CHARACTERIZED
Displayed if Loop 1 output is characterized.
OC2
LOOP 2 OUTPUT
CHARACTERIZED
Displayed if Loop 2 output is characterized.
Σ (Sigma)
CURRENT TOTALIZER VALUE Displays the total flow volume being measured
BIAXXXX
MANUAL RESET VALUE Displays the manual reset value for algorithm
PD+MR.
TUNE OFF
TUNE RUN
ACCUTUNE INDICATION(Note
1)
Appears when Accutune is enabled
Press
to initiate Accutune
Display will read TUNE RUN
OT1
OUTPUT 1 Appears if using Output Override (2 PID loops
only). This value is the calculated Loop 1 internal
value before any override.
Note 1 The value can be changed only in Manual Mode.
Note 2 While viewing Setpoint 1 or Setpoint 2, the value can be changed by using the or
keys. To switch between Setpoint 1 and Setpoint 2, press the SP1/SP2 key
Note 3 To switch between local and remote setpoint, press the RSP/CAS key
Note 4 When viewing the tuning parameters (PID SET1 or PID SET2), the selected set may be
changed using the
or keys.
Note 5 Auxiliary Output is not displayed, but the parameter that it represents is always available
for display.
Comentarios a estos manuales