76 UDC 6300 Process Controller Product Manual 1/03
4.3 Tuning Loop 2 Parameters Set Up Group
Introduction
Tuning L2 (Loop 2) consists of establishing the appropriate values for the
tuning constants for Loop 2 on 2 Loops or Internal Cascade control.
Tuning group
prompts
Table 4-2 lists all the function prompts in the Tuning L2 setup group and
their definitions.
Table 4-2 Tuning L2 (Loop 2) Group Prompt Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PROP BAND3
GAIN 3
RATE3MIN
RESET3MIN or
RESET3RPM
MANRESET3
PROP BAND4
GAIN 4
RATE4MIN
RESET4MIN or
RESET4RPM
CYC3SEC
CYC4SEC
PVEU VAL 1
PVEU VAL 2
PVEU VAL 3
PVEU VAL 4
PVEU VAL 5
PVEU VAL 6
PVEU VAL 7
PVEU VAL 8
GAIN VAL 1
GAIN VAL 2
GAIN VAL 3
GAIN VAL 4
GAIN VAL 5
GAIN VAL 6
GAIN VAL 7
GAIN VAL 8
Same as "TUNING" The definitions listed for the parameters at the left
are the same as those listed previously for the
TUNING parameters Set Up Group except they are
for Loop 2.
The table below shows you how to use them for
Duplex Heat/Cool applications.
DUPLEX OUTPUT RANGES
0 TO 50%-TUNING SETS 2 AND 4:COOL
50 TO 100%-TUNING SETS 1 AND 3: HEAT
Duplex Heat
Output or Loop 1 Loop 2
Range Cool
0 to 50% Cool PID SET 2 PID SET 4
Gain 2 Gain 4
Rate 2 Rate 4
Reset 2 Reset 4
Cycle 2 Cycle 4
50 to 100% Heat PID SET 1 PID SET 3
Gain Gain 3
Rate Rate 3
Reset Reset 3
Cycle Cycle 3