United Security Products AVD-45c Manual Pagina 237

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 302
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 236
1/03 UDC 6300 Process Controller Product Manual 223
6.5 Input #1, 2, 3, or 4 Calibration Procedure, Continued
Table 6-3 Input #1, 2, 3, or 4 Calibration Procedure, continued
Step Description Press Action
3
Calibrate 100 %
FUNC
L1/L2
You will see:
INX SPAN
Lower Display
APPLY
Upper Displa
y
X = 1, 2, 3, or 4
Adjust your calibration device to an output signal
equal to the 100% range value for your particular
input sensor.
4
Exit the Calibration
Mode
FUNC
L1/L2
The controller will store the calibration constants.
or
LOWR
DISP
To exit the calibration mode.
ATTENTION
Press the [FUNC/L1-L2] key first to
store constants.