122 UDC 6300 Process Controller Product Manual 1/03
4.13 Options Set Up Group, Continued
Table 4-12 Option Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
DIG IN 1
DIGITAL INPUT ONE SELECTIONS — Contact
closure enables one of the following (applies to Loop
1 on 2 Loop models).
The controller returns to its original state when
contact opens, except where noted.
If the selection for the Digital Inputs are in conflict
with each other, whichever switch is closed first will
take precedence. If multiple switches are closed
simultaneously, then the lowest numbered Digital
Input takes precedence.
Digital Inputs and Logic Gate outputs configured to
turn on a Digital Output have the same priority.
These operate as an OR function with one another.
The Digital Output will be active if either the Digital
Input or the Gate Output is in a TRUE condition.
If the controller is in Communications Slave mode on
either loop. then the switches are disabled.
NONE
NO DIGITAL INPUT SELECTIONS
TO MAN
TO MANUAL — Contact closure puts the controller
into manual mode.
TO SP1
TO LOCAL SETPOINT — Contact closure puts the
controller into local setpoint 1.
TO SP2
TO LOCAL SETPOINT TWO — Contact closure
puts the controller into local setpoint 2.
TO SP3
TO LOCAL SETPOINT THREE — Contact closure
puts the controller into local setpoint 3.
TO DIRECT
TO DIRECT ACTION — Contact closure selects
direct controller action.
TO HOLD
TO HOLD — Contact closure suspends Setpoint
Ramp. Contact open runs ramp.
TO PID2
TO PID2 — Contact closure selects PID Set 2.
PV IS IN2
PV = INPUT 2-Contact Closure selects PV = Input 2.
PV IS IN3
PV = INPUT 3-Contact Closure selects PV = Input 3.
PV IS IN4
PV = INPUT 4-Contact Closure selects PV = Input 4.
PV IS IN5
PV = INPUT 5-Contact Closure selects PV = Input 5.
TO RUN
RUN — Contact closure starts a stopped SP RAMP.
TRACK 1
OUTPUT 1 TRACKS INPUT 4 — Contact closure
allows OUT 1 to track Input 4.
Table 4-12 continued on next page