64 UDC 6300 Process Controller Product Manual 1/03
3.19 Alarms Set Up Group, Continued
Function prompts,
continued
Table 3-16 lists all the function prompts in the “Alarms” Set Up group.
Table 3-16 Alarms Group Function Prompts, continued
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
A4S1 H L
Alarm 4, Setpoint 1 State LOW
HIGH
HI
A4S2 H L
Alarm 4, Setpoint 2 State LOW
HIGH
LO
AL HYST
Alarm Hysteresis 0.0 to 5.0 % of Output or Span as
appropriate
0.1
ALM ACTN
Alarm Relay Coil Action ENERGIZE
DE ENERGIZ
ENERGIZE
ALM OUT 1
Latching Alarm for
Output 1*
NON LATCH
LATCHING
NON LATCH
ALM OUT 2
Latching Alarm for
Output 2*
NON LATCH
LATCHING
NON LATCH
ALM OUT 3
Latching Alarm for
Output 3*
NON LATCH
LATCHING
NON LATCH
ALM OUT 4
Latching Alarm for
Output 4*
NON LATCH
LATCHING
NON LATCH
* For CE conformity, Performance Criterion A, select ‘NON-