1/03 UDC 6300 Process Controller Product Manual 73
4.2 Tuning Parameters Set Up Group, Continued
Table 4-1 Tuning Group Prompt Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
RSET MIN
or
RSET RPM
0.02 to 50.00
RSET MIN = RESET IN MINUTES / REPEAT
RSET RPM = RESET IN REPEATS PER MINUTE
RESET (Integral Time) adjusts the controller's output
in accordance with both the size of the deviation
(SP-PV) and the time it lasts. The amount of the
corrective action depends on the value of Gain. The
Reset adjustment is measured as how many times
proportional action is repeated/minute or how many
minutes before one repeat of the proportional action
occurs.
Used with control algorithm PID-A or PID-B.
Also defined as "HEAT" Reset on Duplex models for
variations of Heat/Cool applications.
The selection of minutes per repeat or repeats per
minute is made in the “CONTROL” parameters
group under prompt "MINorRPM."
MAN RSET
–100 to +100
(in % output)
MANUAL RESET is only applicable if you use
control algorithm PD WITH MANUAL RESET in the
“Algorithm” Set up group.. Because a proportional
controller will not necessarily line out at setpoint,
there will be a deviation (offset) from setpoint. This
eliminates the offset and lets the PV line out at
setpoint.
Bias appears on the lower display.
PROP BD2
or
GAIN 2
0.1 to 999.9%
or
0.001 to 999.9
PROPORTIONAL BAND 2 or GAIN 2, RATE 2, and
RESET 2 parameters are the same as previously
described for “Heat” except that they refer to the
cool zone tuning constants on duplex models or the
second set of PID constants, whichever is pertinent.
RATE2MIN
0.00 to 10.00 minutes
0.08 or less = OFF
ATTENTION
RSET2MIN
RSET2RPM
0.02 to 50.00 Set 2 Tuning Parameters are not available when
Adaptive Tune selection for Loop 1 is “SP+PV”.
GAIN VALn
Read Only
LOOP 2 GAIN - This is the value being provided by
Gain Scheduling.
CYCLE SEC
1 to 120 seconds
CYCLE TIME (HEAT) determines the length of one
time proportional output relay cycle. Defined as
"HEAT" cycle time for Heat/Cool applications.
CYC2 SEC
1 to 120 seconds
CYCLE TIME 2 (COOL) is the same as above
except it applies to Duplex models as the cycle time
in the "COOL" zone of Heat/Cool applications or for
2nd set of PID constants.
Table 4-1 continued on next page