134 UDC 6300 Process Controller Product Manual 1/03
4.15 Alarms Set Up Group, Continued
Table 4-14 Alarms Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
A3S1 VALU*
Value in Engineering
Units
ALARM 3 SETPOINT 1 VALUE — This is the value
at which you want the alarm type chosen in Prompt
"A3S1TYPE" to actuate. The value depends on what
the setpoint has been configured to represent.
A3S2 VALU*
Value in Engineering
Units
ALARM 3 SETPOINT 2 VALUE — This is the value
at which you want the alarm type chosen in Prompt
"A3S2TYPE" to actuate.
The details are the same as “A1S1 VALU”.
A4S1 VALU*
Value in Engineering
Units
ALARM 4 SETPOINT 1 VALUE — This is the value
at which you want the alarm type chosen in Prompt
"A4S1TYPE" to actuate.
The details are the same as “A1S1 VALU”.
A4S2 VALU*
Value in Engineering
Units
ALARM 4 SETPOINT 2 VALUE — This is the value
at which you want the alarm type chosen in Prompt
"A4S2TYPE" to actuate.
The details are the same as “A1S1 VALU”.
A1S1TYPE
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
PV
DEVIATION
OUTPUT
SHED
PV2
DEV2
OUTPUT2
MANUAL
MANUAL2
REM SP
REM SP2
FAILSAFE
FAILSAFE2
ALARM 1 SETPOINT 1 TYPE — Select what you
want Setpoint 1 of Alarm 1 to represent.
NO ALARM
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
PROCESS VARIABLE
DEVIATION
OUTPUT
SHED FROM COMMUNICATIONS
CONTROL LOOP 2 PV
CONTROL LOOP 2 DEVIATION
CONTROL LOOP 2 OUTPUT
ALARM ON LOOP 1 MANUAL
ALARM ON LOOP 2 MANUAL
ALARM ON LOOP 1 REMOTE SETPOINT
ALARM ON LOOP 2 REMOTE SETPOINT
ALARM ON LOOP 1 FAILSAFE
ALARM ON LOOP 2 FAILSAFE
ATTENTION
When the Alarm type is re-
configured, the value of the current alarm setpoint
does not automatically change to be consistent with
the range of the new alarm type until it is viewed on
the display.
• AxSxVALU is not available for AxSx TYPE: NONE, SHED, MANUAL, MANUAL2, REMSP, REMSP2, FAILSAFE,
FAILSAFE2.