78 UDC 6300 Process Controller Product Manual 1/03
4.4 Setpoint Ramp/Rate Set Up Group, Continued
Setpoint Ramp/ Rate
group prompts,
continued
Table 4-3 Setpoint Ramp/Rate Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
SP RATE
DISABL
ENABLE
ENABLE 2
ENABLE 12
SETPOINT RATE — Lets you configure a specific
rate of change for any local setpoint change. “SP
RAMP” must be disabled.
DISABLE SETPOINT RATE — disables the
setpoint rate option
ENABLE SETPOINT RATE — allows the SP rate
feature for Loop 1
ENABLE SETPOINT RATE 2 — allows the SP rate
feature for Loop 2
ENABLE SETPOINT RATE 12 — allows the SP
rate feature for Loop 1 and Loop 2.
EU/HR UP
0 to 9999 in Engineering
Units per hour
RATE UP — Rate up value for Loop 1. When
making a setpoint change, this is the rate at which
the controller will change from the original setpoint
up to the new one. The ramping (current) setpoint
can be viewed as SPn in the lower display.
Entering a 0 will imply an immediate change in
Setpoint (i.e. no rate applies).
EU/HR DN
0 to 9999 in Engineering
Units per hour
RATE DOWN — Rate down value for Loop 1. When
making a setpoint change, this is the rate at which
the controller will change from the original setpoint
down to the new one. The ramping (current) setpoint
can be viewed as SPn in the lower display.
Entering a 0 will imply an immediate change in
Setpoint (i.e. no rate applies).
EU/HR UP2
0 to 9999 in Engineering
Units per hour
RATE UP — Rate up value for Loop 2. When
making a setpoint change, this is the rate at which
the controller will change from the original setpoint
up to the new one. The ramping (current) setpoint
can be viewed as SPn in the lower display.
Entering a 0 will imply an immediate change in
Setpoint (i.e. no rate applies).
EU/HR DN 2
0 to 9999 in Engineering
Units per hour
RATE DOWN — Rate down value for Loop 2. When
making a setpoint change, this is the rate at which
the controller will change from the original setpoint
down to the new one. The ramping (current) setpoint
can be viewed as SPn in the lower display.
Entering a 0 will imply an immediate change in
Setpoint (i.e. no rate applies).