1/03 UDC 6300 Process Controller Product Manual 53
3.14 Input 5 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 5.
Function prompts
Table 3-11 lists all the function prompts in the INPUT 5 Set Up group.
Table 3-11 Input 5 Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
IN 5 TYPE
Input 5 Type
ATTENTION
Change
of input type selection
results in loss of any field
calibration and restores
factory calibration.
DISABLE
B TC 100 PT
E TC 100 PT LO
J TC 200 PT
K TC 500 PT
NNM TC RH RADIAM
NIC TC MILLIAMPS
R TC
0–10MV
S TC 10–50MV
T TC 1–5V
W TC 0–10V
PULSE
DISABLE
IN5 PULSE
Input 5 Actuation when a
Pulse Input Board is used
DISABLE
FREQ INP
PULSE
DISABLE
XMITTER5
Transmitter
Characterization
DISABLE
B TC T TC
E TC W TC
J TC 100 PT
K TC 100 PT LO
NNM TC 200 PT
NIC TC 500 PT
R TC LINEAR
S TC
SQROOT
LINEAR
IN5 HIGH
Input 5 High Range Value –999 to 9999
in engineering units
(Adjustable for linear inputs only)
1000
IN5 LOW
Input 5 Low Range Value –999 to 9999
in engineering units
(Adjustable for linear inputs only)
0
RATIO 5
Input 5 Ratio Value –20.00 to 20.00 1.0
BIAS IN5
Input 5 Bias Value –999 to 9999
in engineering units
0
FILTER 5
Input 5 Filter 0 to 120 seconds
0 = No Filter
0
BURNOUT5
Sensor Break Protection NONE
UP
DOWN
NONE
EMISSIV 5
Emissivity for RH Radiam 0.01 to 1.00 1.0