2 UDC 6300 Process Controller Product Manual 1/03
1.1 Introduction, Continued
Inputs
Four high-level inputs are standard. They can be:
• 1 to 5 Volts,
• 4 to 20 mA, or
• 10 to 50 mA
A fifth input is available as an option and can be one of several types:
• a low-level Thermocouple or RTD sensor
• a linear input (mA, Volts, mV, or Radiamatic)
• a pulse counter input for use with frequency output devices. This Pulse
counter input can be used as a frequency input or as a setpoint adjustment
input whereby each pulse is counted as one least significant digit change
to the setpoint. A digital input selection determines the direction of
setpoint change.
Any input can be used as:
• the process variable for either loop
• remote setpoint signal
• for computing the weighted average of two inputs
• Input for Math algorithms such as feedforward Summer or Multiplier,
Input Summing with Ratio and Bias, HI/LO Input Select with Ratio and
Bias, Multiplier/Divider.
Outputs
The controller has a current output and is available with an optional
second current output for control, or a signal representing any of several
controller parameters for control or recording purposes.
Output Algorithms
Depending on how many loops you configure, the UDC6300 is available
with various preselected output algorithms including:
On/Off,
• On/Off Duplex,
• Time Proportional Simplex or Duplex,
• Current Proportional Simplex or Duplex,
• Current/Time Duplex.
Digital Inputs /
Outputs
Four points, each of which can be an open-collector type Digital Output
for alarm and control, or a Digital Input. There are also two dedicated
Digital Inputs.
Continued on next page